Cảm biến ngọn lửa và bộ khuếch đại
C7076 UV flame detector
- Flame detector sensor C7076 can detect flame 5 meters distance
- Detecting flames by detecting radiation
- Customizable dual sensitivity. of the sensor
Flame Detector C7076 has sensitivity adjustment device for sensing ultraviolet radiation emitted from gas, oil and tiny flame.The machine is designed for burner management and flame safety monitoring for systems requiring high sensitivity
C7076A used in industrialenvironment
C7076F used in explosion-proof . environment Flame detector sensor designed for use with iR7476 Auto-Test UV Amplifier
Aluminum and cadmium plated steel housing meets NEMA4 standard
- Operating temperature : C7076A/F: - 40 to 70 ˜ C (- 40 to +160 ˜ F)
- Storage temperature: 51 to +85 ˜ C (- 60 to +185 ˜ F)
Working pressure:
- C7076A: up to 138 kPa
- C7076F: up to 500 kPa.
Protection standard:
- C7076A : NEMA 4 compliant
- C7076F: IP65 according to DIN 40050
Mass:
- C7076A: 3.3 kg (7.3 lb).
- C7076F: 6.3 kg (13.9 lb)
Connection standard:
- C7076A: NPT input 1 inch , NPT connector 3/8 inch
- C7076F: Detector with 1 inch NPT probe
- Sensor installation position: Sensor is placed perpendicular (90) horizontally or vertically to get the best results